Application illustrationsPage contents boxguttersDetail sheet 1
Notes:1 The girth of the box gutter and its related drain pipes must be adequate to cope with the expected run off of water. 2. The base of all box gutters are to be sloped. 3. Periodic inspection and cleaning of box gutters is essential. 4. It is suggested that the stopends be lower than both the upstand and inner face of the box gutter to prevent flooding of the roof areas in the event of flash floods. Box Gutters |
Back to contents Expansionjoint – raisedDetail sheet 2
Notes:1 Roof structures are to have sufficient expansion joints to enable it to cope with all expected expansion and contraction. 2. When specifying the waterproofing system both its compatibility and the co-efficient of expansion must be taken into account. 3. Due to the varied nature of the components employed to waterproof expansion joints, close co-operation between the manufacturer/contractor and specifying bodies is required. Expansion Joint Raised |
Back to contents Expansionjoint – levelDetail sheet 3
Notes:1 Roof structures are to have sufficient expansion joints to enable it to cope with all expected expansion and contraction. 2. When specifying the waterproofing system both its compatibility and the co-efficient of expansion must be taken into account. 3. Due to the varied nature of the components employed to waterproof expansion joints, close co-operation between the manufacturer/contractor and specifying bodies is required. Expansion Joint Level |
Back to contents Parapets – higher than 0,5mDetail sheet 4
Notes:1 The groove is situated not less than 200m above the roof/screed. 2. The size and shape of the groove may vary depending on the waterproofing system used. 3. The joint filler used must be compatible with the waterproofing system. High Parapet |
Back to contents Parapets – lower than 0,5mDetail sheet 6
Notes:1. The waterproofing system should be kept away from the outer edge of the parapet for aesthetic reasons and should be firmly secured to prevent wind uplift. 2. A DPC should be included where brick walling is used. Low Parapet |
Back to contents PlantersDetail sheet 7
Notes:1. The diameter of the weep holes must be sufficient to enable the waterproofing system to be dressed into it, and still allow the required amount of water through. 2. The placement of planters should be considered carefully, to ensure that they do not interfere with sensitive areas such as expansion joints, outlets etc. 3. Care must be taken not to damage the waterproofing system while the protection is being installed. 4. The suitability of the waterproofing system should be checked at the design stage with regard to soils, acids, alkalis and root growth etc, to prevent damage from going unnoticed. Planters |
Back to contents Rain water outletsDetail sheet 8
Notes:1. Sufficient outlets must be provided in relation to the size of the catchment area and the expected rainfall. 2. The diameters of the downpipes must be sufficient to cope with the expected water. 3. Carefull attention must be given to dressing the waterproofing system into the rain water outlet. 4. Rain water outlets must never be situated in or through an expansion joint. 5. All outlets must be supplied with hail/leaf guards to prevent blockage. Outlet |
Back to contents Rain water outlets - sideDetail sheet 9 
Notes:1. Sufficient outlets must be provided in relation to the size of the catchment area and the expected rainfall. 2. The diameters of the downpipes must be sufficient to cope with the expected water. 3. Carefull attention must be given to dressing the waterproofing system into the rain water outlet. 4. All outlets must be supplied with hail/leaf guards to prevent blockage. Outlet - side |
Back to contents Tanking - externalDetail sheet 10
Notes:1. The suitability of the waterproofing system should be checked at the design stage with regard to soils, acids, alkalis and root growth etc. 2. Care must be taken not to damage the waterproofing system while the protection wall is being erected. 3. The waterproofing system underfoot should at all times be protected, eg. Screed protection layer. 4. It is advisable to inspect the waterproofing system prior to backfilling or the installation of the wear surface to prevent damage from going unnoticed. External Tanking |
Back to contents Trafficable surface over insulated roofDetail sheet 11
Notes:1. The flashing system indicated above may vary depending on the waterproofing system employed. 2. The trafficable surface is to have sufficient expansion joints to enable it to cope with the expected expansion and contraction (refer to SABS Code of practice – 021) eg. Expansion joints at 3m intervals. 3. When specifying the waterproofing system both its compatibility and co-efficient of expansion must be taken into consideration. 4. It is advisable to inspect the waterproofing system prior to the installation of the trafficable surface to prevent damage from going unnoticed. 5. The insulation material to be used must be given carefull consideration to ensure that it will meet all requirements eg. Point loading, water absorption etc. Trafficable Surface |
Back to contents Thermoflex Dual Waterproofingsystem Dual-reinforced torch-on bitumen membraneDiscussionTHERMOFLEX DUAL is a pre fabricated modified bitumen membrane whose compound is composed of distilled bitumen and elasto-plastermers (APP), reinforced with non-woven polyester fabric and fibre glass matt. This THERMOFLEX DUAL compound offers good ageing properties, flexibility, durability, and elasticity. THERMOFLEX DUAL is available with a talc finish on the upper face to prevent the roll from sticking to itself and benefits the unrolling of the product during installation. The talc finish also enhances the adhesion of aluminium reflective coatings and acrylic paints after application. The lower face of THERMOFLEX DUAL is backed by a special polyethylene burn-off film which melts during torching and prevents the roll from sticking to itself. The correct application temperature is visible from the embossed surface of the membrane which is below the burn off film, when the correct application temperature is reached, this embossment melts, also helping vapour diffusion and avoiding blistering. The burn off film also has a printed10cm square which allows the alignment of the side laps quickly and easily during application. THERMOFLEX DUAL offers a high static and dynamic puncture resistant, good tensile strength, both longitudinal and transversal, ultimate elongation and exceptional dimensional stability. Properties | Specific Gravity: | 1.3 – 1.4 | | Water Vapor Permeability: | Impermeable | | Chemical Resistance: | Resistant to mild acids and alkali solutions.Not resistant to hydro-carbon solvents, diesel | | Slump Resistance: | Will not slump on a vertical surface at 95 c | | Penetration(100g/5s/70c) : | 50-60 | | Cold Flexibility(20mm mandrel) | < 5c 0 | | Elongation @ 25c : | >25% | | Tensile Strength : | >900 N/5cm | | Tear Resistance : | >300 N |
Thermoflex Dual |
|